SF6 Load breaker switch Model: GSC-SC6 12/24kV
Safe epoxy enclosure, high corrosion resistance, low leakage rate,
with switch status observation window which is convenient to observe the switch status.
with a pressure release channel available to equip optional SF6 gas pressure meter.
Economic and cost-effective, easy to form complete set switchgear,low maintenance costs,
working life span is at least 30 years.Extremely reliable and has been widely used,
mature technology, three-position switch, simple and reliable natural interlock.
Description
|
Unit
|
SC6-SIC 24/630
LBS
|
SC6-SQC 24/630
|
Rated voltage
|
kV
|
24
|
Rated frequency
|
Hz
|
50
|
Rated current
|
A
|
630
|
Rated mainly active load-breaking current
|
A
|
630
|
Rated short-circuit making current
|
kA
|
50
|
Rated cable-charging breaking current
|
A
|
10
|
Rated duration of short-circuit
|
s
|
3
|
Rated short time power frequency withstand voltage
|
kV
|
50
|
Rated lightning impulse withstand voltage (Interrupting gap)
|
(kV)
|
145
|
Rated peak withstand current
|
kA
|
50
|